CG170-20B Gas Generator Set

Key Specs

  • Continuous Rating 2300 ekW @1.0pf
  • Fuel Type Natural Gas, Biogas, Coal Gas, Hydrogen Blend (up to 25%)
  • Maximum Electrical Efficiency 45.00%

Benefits

Cogeneration Up to 13%

Savings

On owning and operating costs from improved efficiency

Digital Plant Control

Total Plant and Energy Management System (TPEM) gives you comprehensive and flexible digital control of your generator set's efficiency and performance helping to reduce planning and installation costs.

Up to 25%

hydrogen blended fuel option

Enables operation of up to 25% hydrogen blend (by volume) with pipeline natural gas fuel.

Generator Set Specifications

Continuous Rating 2300 ekW @1.0pf
Fuel Type Natural Gas, Biogas, Coal Gas, Hydrogen Blend (up to 25%)
Maximum Electrical Efficiency 45.00%
Maximum Standby Rating 2300
Frequency 50/60 Hz
RPM 1500 rpm

Engine Specifications

Engine Model CG170B-20
Aspiration TA
Bore 6.7in
Stroke 7.7in

Generator Set Dimensions

Length 258in
Width 67in
Height 89in
Dry Weight - Genset 47377lb

High Efficiency, Lower Operating Costs

  • Up to 45% electrical efficiency with Natural Gas
  • 43.6% electrical efficiency with biogas
  • Electrical output up to 2,300 kWel
  • Reduced vibration and stress on components

Compact Size, High Profitability

  • Compact design that delivers up to 15% more power output at the same size as its predecessor
  • Long maintenance intervals (up to 80,000 hours)
  • Available in different applications, such as natural gas, biogas, wellhead- and propane gas operation
  • Maximum flexibility through different engine variants

Optimized Lubrication Consumption

  • Consumes ~0.15g/kWh
  • Reduced lube oil temperature through better cooling performance
  • Savings of up to 3,000 liters of lube oil per year compared to comparable gensets

Standard Equipment

  • Air Inlet
    • One-element single-stage air cleaner with enclosure and sevice indicator
    • Turbocharger with a water-cooled bearing case for all cylinder
  • Control Panels
    • TPEM (Total Plant & Energy Management System)
  • Cooling
    • Jacket water and SCAC thermostats
    • flange connections for JW inlet and outlet
    • ANSI/DN customer flange connections for JW inlet and outlet
    • Electrical jacket water and aftercooler coolant pump
  • Exhaust
    • PEARL/Low resistence exhaust system
    • Exhaust waste gate for the CG170B-20
    • Closed crankcase ventilation system
  • Fuel System
    • Pre-chamber spark plugs
    • Electronic fuel metering valve
    • Independently controlled cylinder monitoring and ignition system
  • Generator
    • Busbar connections
    • Winding temperature detectors
    • grid code generator
    • Reactive droop
    • 3-phase sensing and KVAR/PF control
    • Anti-condensation space heater
    • closed-coupled generator result in no torque transmission to the base frame
  • Starting/charging
    • 24V starting motors
    • Battery disconnect switch
  • General
    • Crankshaft vibration damper and guard

Optional Equipment

  • Cooling
    • CHP skid
  • Grid Code Compliance
    • 50Hz: Germany, Belgium, Great Britain, Italy, Poland, and Netherlands