Cat EGP Switchgear

EGP (Emergency Generator Paralleling) switchgear is used for paralleling multiple generators that are not directly connected to a utility source.

Key Specs

  • Configuration Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications
  • Modes of Operation Multi-unit Island and multi-unit standby mode with optional redundant controls and components.
  • Application LV and MV (208V - 38 kV)

Benefits

Automatic operation

Dead Bus coordination, Load Shed/Load Add functions/ Load-No load Test

Reduced Commissioning Times

High-speed network connections to Caterpillar Generator Set

Flexible Power offerings

UL 891, UL1558, ANSI37.20
-Indoor, Outdoor, E-house

Technical Summary

Configuration Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie and load breakers in conjunction with downstream transfer switches for standby or emergency applications
Modes of Operation Multi-unit Island and multi-unit standby mode with optional redundant controls and components.
Application LV and MV (208V - 38 kV)

Generator Protective Devices

ANSI Protective Devices 15/25, 27/59, 81 O/U, 32, 40, 50, 51

Environmental Parameters

Certifications IBC, CBC, UBC & OSHPD Certified
Control Panel Enclosure NEMA 1 or NEMA 3R Freestanding Construction
Operating Temperature 0°C to 50°C
Storage Temperature -20°C to +60°C
Low Voltage Standards NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
Medium Voltage Standards NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110

EGP Switchgear

  • High Speed Supervisory Network
  • Automatic Start/Stop
  • Automatic “Dead Bus” Coordination
  • Programmable Load Shed / Load Add Functions
  • Networked Engine Communications
  • Generator Protection
  • Engine Tuning
  • Mode Selection
  • Selectable Auto/ Manual Control
  • Password Protection for Protective Settings and Setup
  • Load/No Load Test
  • Touch Screen (HMI) Display
  • NFPA 99/110 Compliant Alarm
  • Annunciation with Audible Horn
  • Engine Control mimic Screen with gauges for RPM, DC Battery Voltage oil Pressure, Engine Coolant temperature, Engine Hours, Number of starts

Standard Equipment

  • Egp Switchgear
    • Choice of 19” Surface Acoustic Wave Color or 15” Resistive Color Touchscreen
    • Emergency Stop Button for each generator
    • Instant Auto Switch
    • Generator Demand Priority Control
    • Audible Alarm & Horn Silence Button
    • Circuit Breaker Control Switch with Indicators

Optional Equipment

  • Data Table Interface
    • * Accomodates interface with a building management system for monitoring all system parameters via Modbus RTU or TCP
  • Supplemental Hardware Synchronization Check Relay (ansi 25 Device)
    • * Provides additional discrete synchronization protection
  • Remote Power Monitoring System
    • * To monitor breaker status, alarms, metering and other operating parameters