XG400 - NATURAL GAS

This new rental package delivers optimal performance, produces fewer greenhouse gasses, and provides the features and flexibility to fully meet the needs of the Rental and Petroleum markets.


SPECIFICATIONS
Generator
Rating 400 ekW (500 kVA) Continuous
Frequency 60Hz
Voltage 208 - 600 V


Engine
Engine CAT CG137-12 TA Gas Engine
Fuel Natural Gas


Dimensions
Width - With Trailer 96 in
Height - With Trailer 162 in


Dimension
Length - With Trailer 9144 ml


Dimensions
Weight - With Trailer, Lube, Oil and Coolant 39500 lb


BENEFITS & FEATURES
Fuel/Emissions Strategy


U.S. EPA Tier 2 for Large Non-road Spark-ignition Engines

CAT® CG137-12 TA Gas Engine


        
  • Robust high speed diesel block design provides prolonged life and lower owning and operating costs.
  •     
  • Engine ratings developed to accept low-quality gas down to Cat MN 30

CAT EMCP 4.4 Control Panel


Fully featured power metering, protective relaying, and engine/generator control and monitoring.

Cat Generator


        
  • Cat SR4B 593 frame generator designed to match performance and output characteristics of the Cat gas engine.
  •     
  • Segregated AC/DC, low voltage accessory box provides single point access to accessory connections

CAT Integrated Voltage Regulator (IVR)


Three-phase generator voltage sensing with adjustable volts-per-hertz regulation.

Container


        
  • 30' ISO high cube container.
  •     
  • Sound attenuated air intake louvers
  •     
  • Three lockable personnel doors with panic release.
  •     
  • Meets 75 dB(A) at 7 meters sound performance per SAE J1074

Distribution Panel


600/346V, 480/277V, 240/139V, 208/120V, 3-phase.

Side Customer Access


Side buss bar access door, external access load connection buss bars.

Internal Lighting


Three internal DC lights with one timer installed at the container door.

Rental Ready Features


        
  • Anti-condensation heater 110-120 VAC.
  •     
  • Coolant heater 110-120 VAC.
  •     
  • UL Listed battery charger.

Cooling System


Provides 40 ºC (122 ºF) ambient capability with 0.5 g/bhp-hr NOx per NSPS 2010 at 100% continuous rating.

EQUIPMENT
Standard Equipment

20 Amp battery charger
  • UL/CSA listed 120V
24VDC
  • Single electric starting motor
V12
  • CG137-12 TA
canister-type air cleaner with service indicator
  • Single element
external access load connection buss bars
  • Side buss bar access door
integral oil cooler
  • Pump
three-phase
  • SR4B 593 frame
Control Panel
  • EMCP 4.4 genset mounted controller
Cooling System
  • Package-mounted radiator with vertical air discharge provides 40ºC ambient capability
Enclosure
    • Sound attenuated 75 dB(A) @ 7 m.
    • 30' ISO high cube container.
Exhaust System
    • Catalyst w/spark arresting muffler
    • Crankcase fumes disposal system
Fuel System
    • Gas pressure regulator.
    • Low pressure fuel system.
    • Methane detection.
Mounting System
  • Generator set soft mounted to container floor
General
  • Factory testing of standard generator set