C9 (60 HZ)

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.


SPECIFICATIONS
Generator Set Specifications
Minimum Rating 180 ekW
Maximum Rating 300 ekW
Emissions/Fuel Strategy EU Stage IIIA, Low Fuel Consumption
Voltage 220 to 480 Volts
Frequency 60 Hz
Speed 1800 rpm
Duty Cycle Standby, Prime


Engine Specifications
Engine Model C9 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Bore 4.41 in
Stroke 5.87 in
Displacement 537.01 in³
Compression Ratio 16.1:1
Aspiration Air to Air Aftercooled
Fuel System Hydraulic electronic unit injection
Governor Type Adem™A4


Generator Set Dimensions
Length - Maximum 157 in
Width - Maximum 47.5 in
Height - Maximum 73.5 in


BENEFITS & FEATURES
Cat Generator Set Package


  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets other NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine


  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

SR5 Alternator


  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

EMCP Control Panel


  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System


  • Designed to operate in standard ambient temperatures up to 55°C (131°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications


Cat® generator set packages have been fully prototype tested, and certified torsional vibration analysis reports are available. The packages are designed to meet the NFPA 110 requirement for loading, and conform to the ISO 8528-5 steady state and transient response requirements.

One Safe Source


  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

World Wide Product Support


  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Single-Source Supplier


Fully prototype tested with certified torsional vibration analysis available

World Wide Product Support


Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Caterpillar S•O•S℠ program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products

EQUIPMENT
Standard Equipment

Air Inlet System
  • Air cleaner, light duty with disposable paper filter
  • Turbocharger
Control Panels
  • EMC 4.2
  • Oil temperature displays
  • Control panel protective devices: Earth fault relay ; Earth leakage ground fault ; overload shutdown via breaker ; Low fuel level shutdown ; Low fuel level alarm ; Fuel level sensor
Fuel System
  • Standard open set fuel tank / base supplied
  • Base, formed steel with single wall integral 8-hour fuel tank
  • Integral duel wall fuel tank base
Generators and Generator Attachments
  • 12 leads
  • IP23 protection
  • Voltage regulator (single phase sensing)
  • Power centre, IP22
  • Segregated low voltage (AC/DC) wiring panel
  • Mandatory option circuit breaker, IEC, 3 pole mounted in powercentre
Governing System
  • Cat electronic governor (ADEM A4)
Lube System
  • Oil cooler
  • Lubricating oil
  • Oil drain valves
Mounting System
  • Narrow skid base
  • Captive linear vibration isolators between base and engine-generator
  • Includes lifting provisions and termination points for coolant and lube oil drain lines
Starting / Charging System
  • 5 Amp single battery charger
  • Battery disconnet switch
  • Jacket water heater
  • 24V battery with rack and cables
General
  • Engine and alternator re-paint, Caterpillar Yellow

Optional Equipment

Certifications
  • European certificate for conformance
  • Global certificate fpr CIS
Air inlet system
  • Single element air cleaner
Circuit Breakers
  • 4 Pole (IEC-100% rated) circuit breaker upgrades: 400, 630, 800 and 100 amps
Cooling System
  • Radiator and cooling fan with guard
  • Coolant drain line with valve
  • Fan drive, battery charging alternator drive
  • Caterpillar extended life coolant
  • Radiator duct flange
  • Low coolant temperature alarm
Enclosures
  • Sound attenuated enclosure
  • High ambient sound attenuated enclosure
Exhaust System
  • Stainless steel exhaust flex, gaskets, rain cap & SAE exhaust flange for customer use; shipped loose
  • Mufflers - End in / End out; 10 dBA or 25 dBA attenuation
  • 5 - 6 inch flange adaptor
  • 6 inch flange
  • 5 and 6 inch elbow kits
Generators and Attachments
  • Permanent magnet generator
  • Oversize, AREP, CIP generators

CALL NOW TO LEARN MORE