SPECIFICATIONS
Generator Set Specifications
Minimum Rating 500 ekW
Maximum Rating 600 ekW


Generator Set Configurations
Emissions/Fuel Strategy Low Fuel Consumption


Generator Set Specifications
Voltage 220 to 380 Volts


Engine Specifications
Engine Model C18 ATAAC, I-6, 4-Stroke Water-Cooled Diesel


Generator Set Specifications
Frequency 60 Hz


Engine Specifications
Bore 145 mm (5.71 in)


Generator Set Specifications
Speed 1800 RPM


Engine Specifications
Displacement 18.13 L (1106.36 in3)
Stroke 183 mm (7.2 in)
Compression Ratio 14.5:1
Aspiration Air to Air Aftercooled
Governor Type Adem™A4
Fuel System Electronic unit injection


BENEFITS & FEATURES
Cat Diesel Engine


  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

Generator


  • Matched to the performance and output characteristics of Cat engines
  • Industry leading mechanical and electrical design
  • Industry leading motor starting capabilities
  • High Efficiency

Cat EMCP Control Panel


The EMCP controller features the reliability and durability you have come to expect from your Cat equipment. EMCP4 is a scalable control platform designed to ensure reliable generator set operation, providing extensive information about power output and engine operation. EMCP4 systems can be further customized to meet your needs through programming and expansion modules.

Seismic Certification


  • Seismic Certification available.
  • Anchoring details are site specific, and are dependent on many factors such as generator set size, weight, and concrete strength.
  • IBC Certification requires that the anchoring system used is reviewed and approved by a Professional Engineer
  • Seismic Certification per Applicable Building Codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007, CBC 2010
  • Pre-approved by OSHPD and carries an OSP-0321-10 for use in healthcare projects in California

Design Criteria


The generator set accepts 100% rated load in one step per NFPA 110 and meets ISO 8528-5 transient response.

Single-Source Supplier


Fully prototype tested with certified torsional vibration analysis available

World Wide Product Support


Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Caterpillar S•O•S℠ program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products

UL 2200 / CSA - Optional


  • UL 2200 listed packages
  • CSA Certified
  • Certain restrictions may apply.
  • Consult with your Cat® Dealer.

EQUIPMENT
Standard Equipment

Air Inlet
  • Air Cleaner
Cooling
  • Package mounted radiator
Exhaust
  • Exhaust flange outlet
Fuel
  • Primary fuel filter with integral water separator
  • Secondary fuel filter
  • Fuel priming pump
Generator
  • Matched to the performance and output characteristics of Cat engines
  • Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time
  • IP23 Protection
Power Termination
  • Bus Bar
Control Panel
  • EMCP 4.2
Mounting
  • Rubber vibration isolators
Starting/Charging
  • 24 volt starting motor
  • Batteries
General
  • Paint - Caterpillar Yellow except rails and radiators gloss black

Optional Equipment

Exhaust
  • Industrial, Residential, Critical Mufflers
Generator
  • Excitation: [ ] Permanent Magnet Excited (PM) [ ] Internally Excited (IE)
  • Anti-condensation heater
  • Oversize and premium generators
Power Termination
  • Circuit breakers, UL listed
  • Circuit breakers, IEC compliant
Control Panels
  • EMCP 4.4
  • Local & remote annunciator modules
  • Load share module
  • Digital I/O module
  • Remote monitoring software
Starting/Charging
  • Battery chargers
  • Oversize batteries
  • Jacket water heater
  • Heavy-duty starting system
  • Charging alternator
General
  • The following options are based on regional and product configuration:
  • Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
  • UL 2200 package
  • EU Certificate of Conformance (CE)
  • CSA Certification
  • EEC Declaration of Conformity
  • Narrow, Wide or Skid Base
  • Sound attenuated, weather protective or high ambient weather protective enclosure
  • Enclosures: sound attenuated, weather protective
  • Single or dual wall integral fuel tanks
  • Single or dual wall sub-base fuel tanks
  • Integral & sub-base UL listed dual wall fuel tanks
  • Automatic transfer switches (ATS)

CALL NOW TO LEARN MORE

Andy Downs
423-463-2131 or 423-698-6943

Neal Reinhardt
865-595-1034 or 865-771-1036


HOW CAN WE HELP?
SHARE YOUR FEEDBACK OR ASK A QUESTION
Feel free to ask a question or share a comment about the information on this page.

To help us answer your question or respond to your comment, please enter your email address.