C18 (50 HZ) CHINA NON ROAD

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.


SPECIFICATIONS
Generator Set Specifications
Minimum Rating 550 kVA
Maximum Rating 715 kVA
Emissions/Fuel Strategy Low Fuel, EU Stage IIIA
Voltage 380 to 415 Volts
Frequency 50 Hz
Speed 1500 rpm
Duty Cycle Standby, Prime


Engine Specifications
Engine Model C18 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Bore 5.71 in
Stroke 7.2 in
Displacement 1106.4 in³
Compression Ratio 14.5:1
Aspiration Air to Air Aftercooled
Fuel System Electronic unit injection
Governor Type Adem™A4


Generator Set Dimensions
Width - Maximum 80.9 in
Height - Maximum 107.8 in


BENEFITS & FEATURES
Cat Generator Set Package


  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine


  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

SR5 Alternator


  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

EMCP Control Panel


  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System


  • Designed to operate in standard ambient temperatures up to 55°C (131°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications


Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Caterpillar S•O•S℠ program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products

One Safe Source


  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

World Wide Product Support


  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

EQUIPMENT
Standard Equipment

Air System
  • Air Cleaner, light duty
  • Turborcharger
Air Inlet
  • Air Cleaner
Control Panel
  • EMCP 4.2
  • EMCP 4 Genset Controller
Cooling
  • Package mounted radiator
Cooling System
  • Coolant drain line with valve
  • Fan drive, battery charging alternator drive
  • Radiator and cooling fan with guard
  • Caterpillar Extended Life Coolant
Exhaust
  • Exhaust flange outlet
Exhaust System
  • Stainless steel exhaust flex, gaskets, raincap and SAE exhaust flange for customer use; shipped loose
Fuel System
  • Standard open set fuel tank / base supplied Base, formed steel with single wall integral 8-hour fuel tank
Fuel
  • Fuel priming pump
  • Secondary fuel filter
  • Primary fuel filter with integral water separator
Generator
  • Matched to the performance and output characteristics of Cat engines
  • IP23 Protection
  • Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time
Generator and Attachments
  • Segregated low voltage (AC / DC) wiring panel
  • Power center, IP22
  • Optional LC frame generator - IP23 Protection,
  • Mandatory Option Rear circuit breaker, IEC, 3 pole, mounted in power center
  • Integrated Voltage Regulator
  • A frame generator - IP21 Protection
Governing System
  • Cat Electronic Governor (ADEM A4)
Power Termination
  • Bus Bar
Lube System
  • Oil drain valves
  • Lubricating oil
Mounting System
  • Captive linear vibration isolators between base and engine-generator includes lifting provisions and termination points for coolant and lube oil drain lines
Starting / Charging
  • 24 Volt battery with rack and cables
Starting/Charging
  • 24 volt starting motor
  • Batteries
Mounting
  • Rubber vibration isolators
General
  • Engine and alternator pre-paint, Caterpillar Yellow
  • Paint - Caterpillar Yellow except rails and radiators gloss black

Optional Equipment

Certifications
  • Global
  • European Certifications - EU certificate of conformance
Exhaust
  • Industrial, Residential, Critical Mufflers
Air Inlet System
  • Dual element air cleaner
  • Single element air cleaner
Generator
  • Oversize and premium generators
  • Excitation: [ ] Permanent Magnet Excited (PM) [ ] Internally Excited (IE)
  • Anti-condensation heater
Power Termination
  • Circuit breakers, IEC compliant
  • Circuit breakers, UL listed
Circuit Breakers
  • 4 Pole (IEC-100% rated) - package mounted
  • 3 Pole (IEC-100% rated) - package mounted
  • Pad-lockable device
  • 4 Pole (IEC-100% rated) - motorized
  • Power terminal strips
  • 3 Pole (IEC-100% rated) - motorized
Control Panel
  • EMCP 4.4
Control Panels
  • Local & remote annunciator modules
  • Digital I/O module
  • Load share module
  • EMCP (4.2) (4.3) (4.4)
  • Remote monitoring software
Control System
  • Local alarm modules
  • Control panel protective devices
  • Remote annunciator modules
  • Volt free contacts
Cooling System
  • Radiator duct flange
Enclosures
  • Sound attenuated enclosures
Starting/Charging
  • Heavy-duty starting system
  • Battery chargers
  • Charging alternator
  • Oversize batteries
  • Jacket water heater
Exhaust System
  • Elbow Kit
  • Mufflers, End in / End out
  • Manifold and turbocharger guard
  • Engine mounted muffler
  • Flange groups; 8 and 10 inch weld flanges and gaskets
Fuel System
  • Integral -Duel wall fuel tank bases
  • Manual fuel transfer system
  • Fuel transfer system
General
  • Integral & sub-base UL listed dual wall fuel tanks
  • UL 2200 package
  • Narrow, Wide or Skid Base
  • Enclosures: sound attenuated, weather protective
  • Sound attenuated, weather protective or high ambient weather protective enclosure
  • EEC Declaration of Conformity
  • Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
  • The following options are based on regional and product configuration:
  • Single or dual wall sub-base fuel tanks
  • Automatic transfer switches (ATS)
  • CSA Certification
  • EU Certificate of Conformance (CE)
  • Single or dual wall integral fuel tanks
Generator and Attachments
  • A frame CIP generator
  • LC frame generator
  • Permanent magnet excitation
  • LC frame oversize generator
  • Space heaters
  • Ingress protection
  • LC frame CIP generator
  • A frame oversize generator
Lube System
  • Manual sump pump
Mounting System
  • Narrow skid base
Starting / Charging System
  • 5 Amp battery charger
  • Jacket water heater
  • Battery disconnect switch

CALL NOW TO LEARN MORE

Andy Downs
423-463-2131 or 423-698-6943

Neal Reinhardt
865-595-1034 or 865-771-1036