C1.5 (60 HZ)

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.


SPECIFICATIONS
Generator Set Specifications
Minimum Rating 12.0 ekW
Maximum Rating 13.2 ekW
Emissions/Fuel Strategy R96/EUIIIa Equivalent
Voltage 110 to 415 Volts
Frequency 60 Hz
Speed 1800 rpm
Duty Cycle Standby, Prime


Engine Specifications
Engine Model Cat® C1.5
Bore 3.3 in
Stroke 3.5 in
Displacement 91.3 in³
Compression Ratio 22.5:1
Aspiration Naturally Aspirated
Fuel System Indirect Injection
Governor Type Mechanical


Generator Set Dimensions
Length - Maximum 55.1 in
Width - Maximum 24.4 in
Height - Maximum 41.5 in


BENEFITS & FEATURES
Cat Generator Set Package


  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets other NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine


  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

SR5 Alternator


  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

EMCP Control Panel


  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System


  • Designed to operate in standard ambient temperatures up to 55°C (131°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications


Cat Dealers provide extensive post sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Cat® SOSSM program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products.

One Safe Source


  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

World Wide Product Support


  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

EQUIPMENT
Standard Equipment

Air Inlet System
  • Air cleaner; light duty with disposable element
Control Panel
  • EMCP 4.1
Exhaust System
  • Stub pipe, gaskets, raincap & SAE exhaust flange for customer use; shipped loose
Generators and Generator Attachments
  • 12 leads
  • IP23 Protection
  • Voltage regulator (single phase sensing)
  • Tower panel, IP22, bottom cable entry
  • Segregated low voltage (AC/DC) wiring panel
  • Circuit breaker, IEC, 3 pole, mounted in tower panel
Governing System
  • Mechanical governing system
Lube System
  • Lubricating oil
  • Oil drain line with valve
Mounting System
  • Captive linear vibration isolators between base and engine-generator
  • Includes lifting provisions and termination points for coolant
Starting / Charging System
  • 12 Volt battery with rack and cables

Optional Equipment

Alternator Options
  • Coastal insulation protection
Certificates
  • Global certification for CIS
  • European upgrade to STD set for CE certificate
Circuit Breakers
  • 4 Pole circuit breaker
  • Pad-locable breaker device
Control Panel Options
  • EMCP 4.2
  • Volt free contacts for common alarm
  • Volt free contacts for genset running
  • Battery charger
  • Emergency stop with key
Cooling System
  • Radiator and cooling fan with guards
  • Coolant drain line with valve
  • Fan drive, battery charging alternator drive
  • Caterpillar extended life coolant
  • Coolant heater
Enclosures
  • Sound attenuated enclosure (GALV)
  • Single point lift for enclosure
Fuel System
  • Standard open set fuel tank / base supplied
  • Base, formed steel with single wall integral 8-hour fuel tank
  • Skidbase for open sets
  • Skidbase for Enclosures
  • DEFRA bunded fuel tank
  • Low fuel level alarm
  • Fuel transfer control
  • 1000 hr extended service interval
  • Base feet
Mounting Options
  • Battery removal
  • Industrial silencer removal
  • Silencer installation kit
Special Test and Inspection
  • PGS test report @ 1.0 power factor
General
  • Engine and alternator pre-paint, Caterpillar yellow
  • Radiator Stone Guard
  • Packing Case - compact set
  • Packing case - canopied set

CALL NOW TO LEARN MORE

Andy Downs
423-463-2131 or 423-698-6943

Neal Reinhardt
865-595-1034 or 865-771-1036