SPECIFICATIONS
Generator Set Specifications
Minimum Rating 365 kVA
Maximum Rating 550 kVA
Voltage 208 to 600 Volts
Frequency 50 Hz
Speed 1500 RPM


Generator Set Configurations
Emissions/Fuel Strategy Low Fuel Consumption, U.S. EPA Certified for Stationary Emergency Use Only (Tier 2 or Tier 3 Nonroad Equivalent Emission Standards), EU Stage IIIA Nonroad Emission Standards, China Nonroad III Emission Standards


Engine Specifications
Engine Model C15 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Compression Ratio 16.1:1
Aspiration Air to Air Aftercooled
Governor Type Adem™A4
Fuel System MEUI
Bore 5.4 in
Displacement 927.56 in³
Stroke 6.75 in


BENEFITS & FEATURES
Cat Diesel Engine


  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

Cat Diesel Engine


  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

Generator


  • Matched to the performance and output characteristics of Cat engines
  • Industry leading mechanical and electrical design
  • Industry leading motor starting capabilities
  • High Efficiency

Generator


  • Matched to the performance and output characteristics of Cat engines
  • Industry leading mechanical and electrical design
  • Industry leading motor starting capabilities
  • High Efficiency

Cat EMCP Control Panel


The EMCP controller features the reliability and durability you have come to expect from your Cat equipment. EMCP4 is a scalable control platform designed to ensure reliable generator set operation, providing extensive information about power output and engine operation. EMCP4 systems can be further customized to meet your needs through programming and expansion modules.

Cat EMCP Control Panel


The EMCP controller features the reliability and durability you have come to expect from your Cat equipment. EMCP4 is a scalable control platform designed to ensure reliable generator set operation, providing extensive information about power output and engine operation. EMCP4 systems can be further customized to meet your needs through programming and expansion modules.

Seismic Certification


  • Seismic Certification available.
  • Anchoring details are site specific, and are dependent on many factors such as generator set size, weight, and concrete strength.
  • IBC Certification requires that the anchoring system used is reviewed and approved by a Professional Engineer
  • Seismic Certification per Applicable Building Codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007, CBC 2010
  • Pre-approved by OSHPD and carries an OSP-0321-10 for use in healthcare projects in California

Design Criteria


The generator set meets transient response and block loading steps as per ISO 8528-5.

World Wide Product Support


Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Caterpillar S•O•S℠ program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products

Single-Source Supplier


Fully prototype tested with certified torsional vibration analysis available

World Wide Product Support


Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Caterpillar S•O•S℠ program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products

Design Criteria


The generator set accepts 100% rated load in one step per NFPA 110 and meets ISO 8528-5 transient response.

EQUIPMENT
Standard Equipment

Air System
  • Air Cleaner - Non Canister disposable paper filter
  • Aftercooler core
  • Turbocharger
Control Panel
  • EMCP 4.4
Cooling System
  • Radiator and cooling fan with guard
  • Coolant drain line with valve
  • Fan drive, battery charging alternator drive
  • Caterpillar Extended Life Coolant
Exhaust
  • Stainless steel exhaust flex, gaskets, raincap & SAE exhaust flange for customer use; shipped loose
Fuel System
  • Standard open set fuel tank / base supplied
  • Base, formed steel with single wall integral 8-hour fuel tank
Generator and Attachments
  • A frame generator - IP21 Protection
  • Optional LC frame generator - IP23 Protection
  • IP23 Protection
  • Integrated Voltage Regulator
  • Power center, IP22
  • Segregated low voltage (AC/DC) wiring panel
  • Mandatory Option circuit breaker, IEC, 3 pole, mounted in power
Governing System
  • Cat Electronic Governor (ADEM A4)
Lube System
  • Lubricating oil
  • Oil drain valves
Mounting System
  • Rubber vibration isolators
Starting/Charging
  • 24 Volt battery with rack and cables
General
  • Engine and alternator pre paint, Caterpillar yellow

Optional Equipment

Air Inlet System
  • Single element air cleaner
  • Dual element air cleaner
Certifications
  • EU certificate of conformance
  • Global certification for CIS
Circuit breakers
  • 3 Pole (IEC-100% rated) circuit breakers - Package mounted
  • 4 Pole (IEC-100% rated) circuit breakers - Package mounted
  • 3 Pole (IEC-100% rated) circuit breakers - Motorised
  • 4 Pole (IEC-100% rated) circuit breakers - Motorised
  • Auxiliary contacts, circuit breaker
  • Shunt trip for IEC circuit breaker
  • Pad-lockable circuit breaker device
  • Power terminal strip
Control Panels
  • EMCP4.2, EMCP 4.4
  • Volt free contacts
  • Local alarm horn
  • Oil temperature displays
  • Protective devices: Earth fault relay ; Earth leakage ground fault relay ; Overload shutdown via breaker ; Low fuel level alarm ; Low fuel level shutdown ; High fuel level alarm ; Fuel level sensor
  • Local annunciator
  • Remote annunciator
Cooling System
  • Radiator duct flange
  • Stone guards
  • Low coolant temperature alarm
Enclosures
  • Sound attenuated enclosures
  • High ambient sound attenuated enclosures
Exhaust System
  • Engine mounted muffler
  • End in / End out mufflers - 10, 25 and 35 dBA attenuation
  • 6 and 8 inch flange GP
  • Flexible exhaust fittings
  • 6 and 8 inch elbow kit
  • Manifold and turbocharger guard
Fuel System
  • Dual wall fuel tank base
  • Manual fuel transfer pump
  • Fuel transfer system controls
Generator and Attachments
  • Ingress protection
  • Permanent magnet generator
  • Space heaters
  • Oversize A frame generator
  • CIP a frame generator
  • LC frame generator
  • Oversize LC frame generator
  • LC frame CIP generator
Lube System
  • Manual sump pump
Mounting System
  • Narrow skid base - replaces standard fuel tank base
Special Test / Reports
  • PGS Test report @ 1.0 power factor
  • PGS Test report @ 0.8 power factor
Starting / Charging System
  • 5 Amp single battery charger
  • Battery disconnect switch

CALL NOW TO LEARN MORE

Andy Downs
423-463-2131 or 423-698-6943

Neal Reinhardt
865-595-1034 or 865-771-1036


HOW CAN WE HELP?
SHARE YOUR FEEDBACK OR ASK A QUESTION
Feel free to ask a question or share a comment about the information on this page.

To help us answer your question or respond to your comment, please enter your email address.