3516C (50 HZ)

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.


SPECIFICATIONS
Generator Set Specifications
Minimum Rating 2500 kVA
Maximum Rating 2750 kVA
Emissions/Fuel Strategy Low Fuel Consumption, Low Emissions
Voltage 380 to 11000 volts
Frequency 50 Hz
Speed 1500 rpm
Duty Cycle Standby, Mission Critical, Prime


Engine Specifications
Engine Model 3516C, ATAAC, V-16,4-Stroke Water-Cooled Diesel
Bore 6.69 in
Stroke 8.46 in
Displacement 4764.73 in
Compression Ratio 14.7:1
Aspiration TA
Fuel System Electronic unit injection
Governor Type Adem™3


Generator Set Dimensions
Length - Maximum 297.4 in
Width - Maximum 108.9 in
Height - Maximum 118.3 in
Dry Weight - Genset (maximum) 39090 lb


BENEFITS & FEATURES
Cat Generator Set Package


  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets other NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements

Cat Diesel Engine


  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

Alternator


    SR5
  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation

EMCP 4 Control Panel


  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements

Cooling System


  • Designed to operate in standard ambient temperatures up to 50°C (122°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities

Certifications


  • IBC Seismic Certification
  • EU Certification of Conformance (CE)
  • EEC Declaration of Conformity

One Safe Source


  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system

World Wide Product Support


  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

EQUIPMENT
Standard Equipment

Air Inlet
  • Air cleaner
Cooling
  • Package mounted radiator
Exhaust
  • Exhaust flange outlet
Fuel
  • Primary fuel filter with integral water separator
  • Secondary fuel filter
  • Fuel priming pump
Generator
  • Matched to the performance and output characteristics of Cat engines
  • IP23 Protection
Power Termination
  • Bus Bar
Control Panel
  • EMCP 4 Genset Controller
General
  • Paint - Caterpillar Yellow except rails and radiators gloss black

Optional Equipment

Exhaust
  • Exhaust mufflers
Generator
  • Anti-condensation heater
  • Excitation: [ ] Permanent Magnet Excited (PM) [ ] Internally Excited (IE)
  • Oversize and premium generators
Power Termination
  • Circuit breakers, UL listed
  • Circuit breakers, IEC compliant
Control Panels
  • EMCP (4.2) (4.3) (4.4)
  • Generator temperature monitoring & protection
  • Load share module
  • Digital I/O module
  • Remote monitoring software
Mounting
  • Rubber anti-vibration mounts
  • Spring-type vibration isolator
  • IBC isolators
Starting/Charging
  • Battery chargers
  • Oversize batteries
  • Jacket water heater
  • Heavy-duty starting system
  • Charging alternator
  • Air starting motor with control and silencer
General
  • The following options are based on regional and product configuration:
  • Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
  • UL 2200 package
  • EU Certificate of Conformance (CE)
  • CSA Certification
  • EEC Declaration of Conformity
  • Enclosures: sound attenuated, weather protective
  • Automatic transfer switches (ATS)
  • Integral & sub-base fuel tanks
  • Integral & sub-base UL listed dual wall fuel tanks

CALL NOW TO LEARN MORE

Andy Downs
423-463-2131 or 423-698-6943

Neal Reinhardt
865-595-1034 or 865-771-1036