3516B (50 HZ)

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.


SPECIFICATIONS
Generator Set Specifications
Minimum Rating 1750 kVA
Maximum Rating 2500 kVA
Emissions/Fuel Strategy Low Fuel Consumption, Low Emissions
Voltage 380 to 11000 Volts
Frequency 50 Hz
Speed 1500 rpm
Duty Cycle Standby, Mission Critical, Prime, Continuous


Engine Specifications
Engine Model 3516B TA, V-16, 4-Stroke Water-Cooled Diesel
Bore 6.69 in
Stroke 7.48 in
Displacement 4210.64 in
Displacement - HD 4764.73 in³
Compression Ratio 14.0:1 Std 15.5:1 HD
Aspiration TA
Fuel System Electronic unit injection
Governor Type Adem™3


Generator Set Dimensions
Length - Minimum 233.4 in
Length - Maximum 251.7 in
Width - Maximum 90 in
Height - Maximum 93.2 in
Dry Weight - Genset (minimum) 31900 lb
Dry Weight - Genset (maximum) 40320 lb


BENEFITS & FEATURES
Cat Diesel Engine


  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight

Generator


  • Matched to the performance and output characteristics of Cat engines
  • Industry leading mechanical and electrical design
  • Industry leading motor starting capabilities
  • High Efficiency

Cat EMCP Control Panel


The EMCP controller features the reliability and durability you have come to expect from your Cat equipment. EMCP4 is a scalable control platform designed to ensure reliable generator set operation, providing extensive information about power output and engine operation. EMCP4 systems can be further customized to meet your needs through programming and expansion modules.

Seismic Certification


  • Seismic Certification available.
  • Anchoring details are site specific, and are dependent on many factors such as generator set size, weight, and concrete strength.
  • IBC Certification requires that the anchoring system used is reviewed and approved by a Professional Engineer
  • Seismic Certification per Applicable Building Codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007, CBC 2010
  • Pre-approved by OSHPD and carries an OSP-0321-10 for use in healthcare projects in California

Design Criteria


The generator set accepts 100% rated load in one step per NFPA 110 and meets ISO 8528-5 transient response.

UL 2200 / CSA - Optional


  • UL 2200 listed packages
  • CSA Certified
  • Certain restrictions may apply.
  • Consult with your Cat® Dealer.

Single-Source Supplier


Fully prototype tested with certified torsional vibration analysis available

World Wide Product Support


Cat Dealers provide extensive post sale support including maintenance and repair agreements. Cat dealers have over 1,800 dealer branch stores operating in 200 countries. The Cat® SOSSM program cost effectively detects internal engine component condition, even the presence of unwanted fluids and combustion by-products.

EQUIPMENT
Standard Equipment

Air Inlet
  • Air cleaner
Cooling
  • Package mounted radiator
Exhaust
  • Exhaust flange outlet
Fuel
  • Primary fuel filter with integral water separator
  • Secondary fuel filter
  • Fuel priming pump
Generator
  • Matched to the performance and output characteristics of Cat engines
  • IP23 Protection
Power Termination
  • Busbar
Control Panel
  • EMCP 4
General
  • Paint - Caterpillar Yellow except rails and radiators gloss black

Optional Equipment

Exhaust
  • Exhaust mufflers (except Tier 4)
Generator
  • Anti-condensation heater
  • Internal excitation (IE)
  • Permanent magnet excitation (PMG)
  • Oversize and premium generators
Power Termination
  • Circuit breakers, UL listed
  • Circuit breakers, IEC compliant
Control Panels
  • EMCP 4.2, EMCP 4.3, EMCP 4.4
  • EMCP 4.3
  • EMCP 4.4
  • Generator temperature monitoring & protection
  • Load share module
  • Digital I/O module
  • Remote monitoring software
Mounting
  • Rubber anti-vibration mounts
  • Spring-type vibration isolator
  • IBC isolators
Starting/Charging
  • Battery chargers
  • Oversize batteries
  • Jacket water heater
  • Heavy-duty starting system
  • Charging alternator
  • Air starting motor with control and silencer
General
  • The following options are based on regional and product configuration:
  • Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
  • UL 2200 package
  • EU Certificate of Conformance (CE)
  • CSA Certification
  • EEC Declaration of Conformity
  • Enclosures: sound attenuated, weather protective
  • Automatic transfer switches (ATS)
  • Integral & sub-base fuel tanks
  • Integral & sub-base UL listed dual wall fuel tanks